Total 821 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2017-7966 1 Schneider-electric 1 Somachine 2025-04-20 N/A
A DLL Hijacking vulnerability in the programming software in Schneider Electric's SoMachine HVAC v2.1.0 allows a remote attacker to execute arbitrary code on the targeted system. The vulnerability exists due to the improper loading of a DLL.
CVE-2017-7965 1 Schneider-electric 1 Somachine Hvac 2025-04-20 7.3 High
A buffer overflow vulnerability exists in Programming Software executable AlTracePrint.exe, in Schneider Electric's SoMachine HVAC v2.1.0 for Modicon M171/M172 Controller.
CVE-2017-7689 1 Schneider-electric 2 Homelynk Controller Lss100100, Homelynk Controller Lss100100 Firmware 2025-04-20 9.8 Critical
A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0.
CVE-2016-5809 1 Schneider-electric 6 Ion5000, Ion7300, Ion7500 and 3 more 2025-04-20 N/A
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of this vulnerability can allow unauthorized configuration changes to be made and saved.
CVE-2017-9631 1 Schneider-electric 1 Wonderware Archestra Logger 2025-04-20 7.5 High
A Null Pointer Dereference issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The null pointer dereference vulnerability could allow an attacker to crash the logger process, causing a denial of service for logging and log-viewing (applications that use the Wonderware ArchestrA Logger continue to run when the Wonderware ArchestrA Logger service is unavailable).
CVE-2017-6033 1 Schneider-electric 1 Interactive Graphical Scada System 2025-04-20 N/A
A DLL Hijacking issue was discovered in Schneider Electric Interactive Graphical SCADA System (IGSS) Software, Version 12 and previous versions. The software will execute a malicious file if it is named the same as a legitimate file and placed in a location that is earlier in the search path.
CVE-2017-7971 1 Schneider-electric 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert 2025-04-20 N/A
A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the use of outdated cipher suites and improper verification of peer SSL Certificate.
CVE-2017-7907 1 Schneider-electric 1 Wonderware Historian Client 2025-04-20 N/A
An Improper XML Parser Configuration issue was discovered in Schneider Electric Wonderware Historian Client 2014 R2 SP1 and prior. An improperly restricted XML parser (with improper restriction of XML external entity reference, or XXE) may allow an attacker to enter malicious input through the application which could cause a denial of service or disclose file contents from a server or connected network.
CVE-2020-25178 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 7.5 High
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.
CVE-2020-25182 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 6.7 Medium
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems.
CVE-2020-25176 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 9.1 Critical
Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution.
CVE-2020-25184 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 7.8 High
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x stores the password in plaintext in a file that is in the same directory as the executable file. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification. A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure.
CVE-2020-25180 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 5.3 Medium
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.
CVE-2016-4529 1 Schneider-electric 3 M171, M172, Somachine Hvac Firmware 2025-04-12 7.3 High
An unspecified ActiveX control in Schneider Electric SoMachine HVAC Programming Software for M171/M172 Controllers before 2.1.0 allows remote attackers to execute arbitrary code via unknown vectors, related to the INTERFACESAFE_FOR_UNTRUSTED_CALLER (aka safe for scripting) flag.
CVE-2014-8390 1 Schneider-electric 1 Vampset 2025-04-12 N/A
Multiple buffer overflows in Schneider Electric VAMPSET before 2.2.168 allow local users to gain privileges via malformed disturbance-recording data in a (1) CFG or (2) DAT file.
CVE-2015-7918 1 Schneider-electric 1 Proclima 2025-04-12 N/A
Multiple buffer overflows in the F1BookView ActiveX control in F1 Bookview in Schneider Electric ProClima before 6.2 allow remote attackers to execute arbitrary code via the (1) Attach, (2) DefinedName, (3) DefinedNameLocal, (4) ODBCPrepareEx, (5) ObjCreatePolygon, (6) SetTabbedTextEx, or (7) SetValidationRule method, a different vulnerability than CVE-2015-8561.
CVE-2014-8511 1 Schneider-electric 1 Proclima 2025-04-12 N/A
Buffer overflow in an ActiveX control in Atx45.ocx in Schneider Electric ProClima before 6.1.7 allows remote attackers to execute arbitrary code via unspecified vectors, a different vulnerability than CVE-2014-8512. NOTE: this may be clarified later based on details provided by researchers.
CVE-2013-0662 2 Schneider-electric, Schneider Electric 13 Concept, Modbus Serial Driver, Modbuscommdtm Sl and 10 more 2025-04-12 N/A
Multiple stack-based buffer overflows in ModbusDrv.exe in Schneider Electric Modbus Serial Driver 1.10 through 3.2 allow remote attackers to execute arbitrary code via a large buffer-size value in a Modbus Application Header.
CVE-2016-2291 1 Schneider-electric 4 Proface Gp-pro Ex Ex-ed, Proface Gp-pro Ex Pfxexedls, Proface Gp-pro Ex Pfxexedv and 1 more 2025-04-12 6.5 Medium
Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 allow remote attackers to execute arbitrary code or cause a denial of service (out-of-bounds read) via unspecified vectors.
CVE-2016-2292 1 Schneider-electric 4 Proface Gp-pro Ex Ex-ed, Proface Gp-pro Ex Pfxexedls, Proface Gp-pro Ex Pfxexedv and 1 more 2025-04-12 6.5 Medium
Stack-based buffer overflow in Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 allows remote attackers to execute arbitrary code via unspecified vectors.