Filtered by vendor Schneider-electric
Subscriptions
Total
806 CVE
| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2018-7798 | 1 Schneider-electric | 2 Modicon M221, Somachine Basic | 2026-05-29 | 8.2 High |
| A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mask and gateway) when remotely connected to the device. | ||||
| CVE-2022-0715 | 1 Schneider-electric | 66 Scl Series 1029 Ups, Scl Series 1029 Ups Firmware, Scl Series 1030 Ups and 63 more | 2026-05-29 | 8.9 High |
| A CWE-287: Improper Authentication vulnerability exists that could cause an attacker to arbitrarily change the behavior of the UPS when a key is leaked and used to upload malicious firmware. Affected Product: APC Smart-UPS Family: SMT Series (SMT Series ID=18: UPS 09.8 and prior / SMT Series ID=1040: UPS 01.2 and prior / SMT Series ID=1031: UPS 03.1 and prior), SMC Series (SMC Series ID=1005: UPS 14.1 and prior / SMC Series ID=1007: UPS 11.0 and prior / SMC Series ID=1041: UPS 01.1 and prior), SCL Series (SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior), SMX Series (SMX Series ID=20: UPS 10.2 and prior / SMX Series ID=23: UPS 07.0 and prior), SRT Series (SRT Series ID=1010/1019/1025: UPS 08.3 and prior / SRT Series ID=1024: UPS 01.0 and prior / SRT Series ID=1020: UPS 10.4 and prior / SRT Series ID=1021: UPS 12.2 and prior / SRT Series ID=1001/1013: UPS 05.1 and prior / SRT Series ID=1002/1014: UPSa05.2 and prior), APC SmartConnect Family: SMT Series (SMT Series ID=1015: UPS 04.5 and prior), SMC Series (SMC Series ID=1018: UPS 04.2 and prior), SMTL Series (SMTL Series ID=1026: UPS 02.9 and prior), SCL Series (SCL Series ID=1029: UPS 02.5 and prior / SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior / SCL Series ID=1037: UPS 03.1 and prior), SMX Series (SMX Series ID=1031: UPS 03.1 and prior) | ||||
| CVE-2018-7794 | 1 Schneider-electric | 58 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 55 more | 2026-05-29 | 7.5 High |
| A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon Quantum, Modicon Premium (see security notification for specific versions) which could cause a Denial of Service when reading data with invalid index using Modbus TCP. | ||||
| CVE-2018-7792 | 1 Schneider-electric | 2 Modicon M221, Modicon M221 Firmware | 2026-05-29 | 7.5 High |
| A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to decode the password using rainbow table. | ||||
| CVE-2021-22792 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2026-05-29 | 6.5 Medium |
| A CWE-476: NULL Pointer Dereference vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions). | ||||
| CVE-2018-7791 | 1 Schneider-electric | 2 Modicon M221, Modicon M221 Firmware | 2026-05-29 | 9.8 Critical |
| A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to overwrite the original password with their password. If an attacker exploits this vulnerability and overwrite the password, the attacker can upload the original program from the PLC. | ||||
| CVE-2021-22790 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2026-05-29 | 6.5 Medium |
| A CWE-125: Out-of-bounds Read vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions). | ||||
| CVE-2018-7790 | 1 Schneider-electric | 2 Modicon M221, Modicon M221 Firmware | 2026-05-29 | 9.8 Critical |
| An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the attacker can upload the original program from the PLC. | ||||
| CVE-2021-22779 | 1 Schneider-electric | 61 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 58 more | 2026-05-29 | 6.5 Medium |
| Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller. | ||||
| CVE-2021-22768 | 1 Schneider-electric | 4 Powerlogic Egx100, Powerlogic Egx100 Firmware, Powerlogic Egx300 and 1 more | 2026-05-29 | 9.8 Critical |
| A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet.This CVE ID is unique from CVE-2021-22767 | ||||
| CVE-2018-7789 | 1 Schneider-electric | 2 Modicon M221, Modicon M221 Firmware | 2026-05-29 | 4.8 Medium |
| An Improper Check for Unusual or Exceptional Conditions vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to remotely reboot Modicon M221 using crafted programing protocol frames. | ||||
| CVE-2021-22765 | 1 Schneider-electric | 4 Powerlogic Egx100, Powerlogic Egx100 Firmware, Powerlogic Egx300 and 1 more | 2026-05-29 | 9.8 Critical |
| A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet | ||||
| CVE-2020-7489 | 1 Schneider-electric | 8 Ecostruxure Machine Expert, Modicon M100, Modicon M100 Firmware and 5 more | 2026-05-28 | 9.8 Critical |
| A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection') vulnerability exists on EcoStruxure Machine Expert – Basic or SoMachine Basic programming software (versions in security notification). The result of this vulnerability, DLL substitution, could allow the transference of malicious code to the controller. | ||||
| CVE-2020-7488 | 1 Schneider-electric | 11 Ecostruxure Machine Expert, Modicon M218, Modicon M218 Firmware and 8 more | 2026-05-28 | 7.5 High |
| A CWE-319: Cleartext Transmission of Sensitive Information vulnerability exists which could leak sensitive information transmitted between the software and the Modicon M218, M241, M251, and M258 controllers. | ||||
| CVE-2020-7477 | 1 Schneider-electric | 56 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 53 more | 2026-05-28 | 7.5 High |
| A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Quantum Ethernet Network module 140NOE771x1 (Versions 7.0 and prior), Quantum processors with integrated Ethernet – 140CPU65xxxxx (all Versions), and Premium processors with integrated Ethernet (all Versions), which could cause a Denial of Service when sending a specially crafted command over Modbus. | ||||
| CVE-2020-28220 | 1 Schneider-electric | 4 Modicon M258, Modicon M258 Firmware, Somachine and 1 more | 2026-05-28 | 4.7 Medium |
| A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists in Modicon M258 Firmware (All versions prior to V5.0.4.11) and SoMachine/SoMachine Motion software (All versions), that could cause a buffer overflow when the length of a file transferred to the webserver is not verified. | ||||
| CVE-2020-28214 | 1 Schneider-electric | 2 Modicon M221, Modicon M221 Firmware | 2026-05-28 | 9.8 Critical |
| A CWE-760: Use of a One-Way Hash with a Predictable Salt vulnerability exists in Modicon M221 (all references, all versions), that could allow an attacker to pre-compute the hash value using dictionary attack technique such as rainbow tables, effectively disabling the protection that an unpredictable salt would provide. | ||||
| CVE-2020-7534 | 1 Schneider-electric | 20 140cpu65, 140cpu65 Firmware, 140noc78000 and 17 more | 2026-05-28 | 7.1 High |
| A CWE-352: Cross-Site Request Forgery (CSRF) vulnerability exists on the web server used, that could cause a leak of sensitive data or unauthorized actions on the web server during the time the user is logged in. Affected Products: Modicon M340 CPUs: BMXP34 (All Versions), Modicon Quantum CPUs with integrated Ethernet (Copro): 140CPU65 (All Versions), Modicon Premium CPUs with integrated Ethernet (Copro): TSXP57 (All Versions), Modicon M340 ethernet modules: (BMXNOC0401, BMXNOE01, BMXNOR0200H) (All Versions), Modicon Quantum and Premium factory cast communication modules: (140NOE77111, 140NOC78*00, TSXETY5103, TSXETY4103) (All Versions) | ||||
| CVE-2020-28210 | 1 Schneider-electric | 1 Ecostruxure Building Operation | 2026-05-28 | 6.1 Medium |
| A CWE-79 Improper Neutralization of Input During Web Page Generation (Cross-site Scripting) vulnerability exists in EcoStruxure Building Operation WebStation V2.0 - V3.1 that could cause an attacker to inject HTML and JavaScript code into the user's browser. | ||||
| CVE-2020-28209 | 2 Microsoft, Schneider-electric | 2 Windows, Enterprise Server Installer | 2026-05-28 | 7 High |
| A CWE-428 Windows Unquoted Search Path vulnerability exists in EcoStruxure Building Operation Enterprise Server installer V1.9 - V3.1 and Enterprise Central installer V2.0 - V3.1 that could cause any local Windows user who has write permission on at least one of the subfolders of the Connect Agent service binary path, being able to gain the privilege of the user who started the service. By default, the Enterprise Server and Enterprise Central is always installed at a location requiring Administrator privileges so the vulnerability is only valid if the application has been installed on a non-secure location. | ||||