Filtered by vendor Schneider-electric Subscriptions
Total 789 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2017-5155 1 Schneider-electric 1 Wonderware Historian 2025-04-20 N/A
An issue was discovered in Schneider Electric Wonderware Historian 2014 R2 SP1 P01 and earlier. Wonderware Historian creates logins with default passwords, which can allow a malicious entity to compromise Historian databases. In some installation scenarios, resources beyond those created by Wonderware Historian may be compromised as well.
CVE-2017-6017 1 Schneider-electric 30 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 27 more 2025-04-20 N/A
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover.
CVE-2017-9631 1 Schneider-electric 1 Wonderware Archestra Logger 2025-04-20 7.5 High
A Null Pointer Dereference issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The null pointer dereference vulnerability could allow an attacker to crash the logger process, causing a denial of service for logging and log-viewing (applications that use the Wonderware ArchestrA Logger continue to run when the Wonderware ArchestrA Logger service is unavailable).
CVE-2016-8352 1 Schneider-electric 6 Connexium Firmware, Tcsefec23f3f20, Tcsefec23f3f21 and 3 more 2025-04-20 N/A
An issue was discovered in Schneider Electric ConneXium firewalls TCSEFEC23F3F20 all versions, TCSEFEC23F3F21 all versions, TCSEFEC23FCF20 all versions, TCSEFEC23FCF21 all versions, and TCSEFEC2CF3F20 all versions. A stack-based buffer overflow can be triggered during the SNMP login authentication process that may allow an attacker to remotely execute code.
CVE-2017-7574 1 Schneider-electric 3 Modicon Tm221ce16r, Modicon Tm221ce16r Firmware, Somachine 2025-04-20 9.8 Critical
Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.
CVE-2017-7973 1 Schneider-electric 1 U.motion Builder 2025-04-20 N/A
A SQL injection vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can use calls to various paths allowing performance of arbitrary SQL commands against the underlying database.
CVE-2017-13997 1 Schneider-electric 2 Wonderware Indusoft Web Studio, Wonderware Intouch 2025-04-20 N/A
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.
CVE-2017-7967 1 Schneider-electric 1 Vampset 2025-04-20 N/A
All versions of VAMPSET software produced by Schneider Electric, prior to V2.2.189, are susceptible to a memory corruption vulnerability when a corrupted vf2 file is used. This vulnerability causes the software to halt or not start when trying to open the corrupted file. This vulnerability occurs when fill settings are intentionally malformed and is opened in a standalone state, without connection to a protection relay. This attack is not considered to be remotely exploitable. This vulnerability has no effect on the operation of the protection relay to which VAMPSET is connected. As Windows operating system remains operational and VAMPSET responds, it is able to be shut down through its normal closing protocol.
CVE-2017-9956 1 Schneider-electric 1 U.motion Builder 2025-04-20 N/A
An authentication bypass vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the system contains a hard-coded valid session. An attacker can use that session ID as part of the HTTP cookie of a web request, resulting in authentication bypass
CVE-2017-6030 1 Schneider-electric 6 Modicon M221, Modicon M221 Firmware, Modicon M241 and 3 more 2025-04-20 6.5 Medium
A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.
CVE-2016-5815 1 Schneider-electric 6 Ion5000, Ion7300, Ion7500 and 3 more 2025-04-20 N/A
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes.
CVE-2017-6026 1 Schneider-electric 4 Modicon M241, Modicon M241 Firmware, Modicon M251 and 1 more 2025-04-20 9.1 Critical
A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are lacking randomization and are shared between several users. This may allow a current session to be compromised.
CVE-2017-6028 1 Schneider-electric 4 Modicon M241, Modicon M241 Firmware, Modicon M251 and 1 more 2025-04-20 9.8 Critical
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.
CVE-2017-9959 1 Schneider-electric 1 U.motion Builder 2025-04-20 N/A
A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the system accepts reboot in session from unauthenticated users, supporting a denial of service condition.
CVE-2017-14024 1 Schneider-electric 2 Wonderware Indusoft Web Studio, Wonderware Intouch 2025-04-20 N/A
A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges.
CVE-2017-6033 1 Schneider-electric 1 Interactive Graphical Scada System 2025-04-20 N/A
A DLL Hijacking issue was discovered in Schneider Electric Interactive Graphical SCADA System (IGSS) Software, Version 12 and previous versions. The software will execute a malicious file if it is named the same as a legitimate file and placed in a location that is earlier in the search path.
CVE-2017-7689 1 Schneider-electric 2 Homelynk Controller Lss100100, Homelynk Controller Lss100100 Firmware 2025-04-20 9.8 Critical
A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0.
CVE-2017-7575 1 Schneider-electric 2 Modicon Tm221ce16r, Modicon Tm221ce16r Firmware 2025-04-20 N/A
Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded.
CVE-2016-5809 1 Schneider-electric 6 Ion5000, Ion7300, Ion7500 and 3 more 2025-04-20 N/A
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of this vulnerability can allow unauthorized configuration changes to be made and saved.
CVE-2017-9958 1 Schneider-electric 1 U.motion Builder 2025-04-20 N/A
An improper access control vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an improper handling of the system configuration can allow an attacker to execute arbitrary code under the context of root.